  "name": "Duct Calculator",
  "id": "duct-calculator",
  "publisher": "FieldRanger",
  "description": "Sizes a round duct from airflow (CFM) and friction rate with a velocity check, finds the airflow a given round duct carries, and gives the round equivalent of a rectangular duct.",
  "page": "https://fieldranger.ai/templates/duct-calculator",
  "endpoint": "https://fieldranger.ai/api/tools/duct-calculator",
  "usage": "GET with query parameters, or POST a JSON object with the same names, returns the computed result. GET with no parameters returns this description.",
  "inputs": [
    {
      "name": "mode",
      "label": "Calculate",
      "type": "string (enum)",
      "required": false,
      "default": "size",
      "enum": [
        {
          "value": "size",
          "label": "Duct size from CFM"
        },
        {
          "value": "airflow",
          "label": "CFM from duct size"
        },
        {
          "value": "rectangular",
          "label": "Rectangular equivalent"
        }
      ],
      "description": "Size a duct from airflow, find the airflow a round duct carries, or convert a rectangular duct."
    },
    {
      "name": "ductType",
      "label": "Duct",
      "type": "string (enum)",
      "required": false,
      "default": "supply",
      "enum": [
        {
          "value": "supply",
          "label": "Supply"
        },
        {
          "value": "return",
          "label": "Return"
        }
      ],
      "description": "Sets the velocity limit: 900 fpm for supply, 700 fpm for return."
    },
    {
      "name": "frictionFrom",
      "label": "Friction rate source",
      "type": "string (enum)",
      "required": false,
      "default": "rate",
      "enum": [
        {
          "value": "rate",
          "label": "Enter friction rate"
        },
        {
          "value": "static",
          "label": "Calculate from static pressure"
        }
      ],
      "description": "Enter the friction rate, or calculate it from static pressure and effective length."
    },
    {
      "name": "frictionRate",
      "label": "Friction rate",
      "type": "number",
      "unit": "in. wc per 100 ft",
      "required": false,
      "default": 0.08,
      "defaultIsSample": true,
      "minimum": 0.01,
      "maximum": 1,
      "onlyWhen": "frictionFrom is rate",
      "description": "Design friction rate for the system."
    },
    {
      "name": "esp",
      "label": "External static pressure",
      "type": "number",
      "unit": "in. wc",
      "required": false,
      "default": 0.5,
      "defaultIsSample": true,
      "minimum": 0.05,
      "maximum": 3,
      "onlyWhen": "frictionFrom is static",
      "description": "From the blower table at the design airflow."
    },
    {
      "name": "cpl",
      "label": "Component pressure losses",
      "type": "number",
      "unit": "in. wc",
      "required": false,
      "default": 0.3,
      "defaultIsSample": true,
      "minimum": 0,
      "maximum": 3,
      "onlyWhen": "frictionFrom is static",
      "description": "Coil, filter, registers, grilles and balancing dampers, added together."
    },
    {
      "name": "tel",
      "label": "Total effective length",
      "type": "number",
      "unit": "ft",
      "required": false,
      "default": 250,
      "defaultIsSample": true,
      "minimum": 10,
      "maximum": 3000,
      "onlyWhen": "frictionFrom is static",
      "description": "Longest supply run plus longest return run, with fitting equivalent lengths."
    },
    {
      "name": "cfm",
      "label": "Airflow",
      "type": "number",
      "unit": "CFM",
      "required": false,
      "default": 1200,
      "defaultIsSample": true,
      "minimum": 1,
      "maximum": 100000,
      "onlyWhen": "mode is size",
      "description": "Air the duct must carry: the blower's design airflow for a trunk, the room airflow for a branch."
    },
    {
      "name": "rectHeight",
      "label": "Rectangular height (optional)",
      "type": "number",
      "unit": "in",
      "required": false,
      "minimum": 3,
      "maximum": 60,
      "onlyWhen": "mode is size",
      "description": "Gives the width of a rectangular duct equal to the recommended round size."
    },
    {
      "name": "diameter",
      "label": "Round duct diameter",
      "type": "number",
      "unit": "in",
      "required": false,
      "default": 16,
      "defaultIsSample": true,
      "minimum": 3,
      "maximum": 60,
      "onlyWhen": "mode is airflow",
      "description": "Inside diameter of the round duct."
    },
    {
      "name": "width",
      "label": "Width",
      "type": "number",
      "unit": "in",
      "required": false,
      "default": 20,
      "defaultIsSample": true,
      "minimum": 3,
      "maximum": 120,
      "onlyWhen": "mode is rectangular",
      "description": "Inside width of the rectangular duct."
    },
    {
      "name": "height",
      "label": "Height",
      "type": "number",
      "unit": "in",
      "required": false,
      "default": 8,
      "defaultIsSample": true,
      "minimum": 3,
      "maximum": 120,
      "onlyWhen": "mode is rectangular",
      "description": "Inside height of the rectangular duct."
    }
  ],
  "outputs": [
    {
      "name": "frictionRate",
      "label": "Friction rate",
      "unit": "in. wc per 100 ft",
      "type": "number",
      "description": "Friction rate used, entered or calculated."
    },
    {
      "name": "calculatedDiameterIn",
      "label": "Calculated diameter",
      "unit": "in",
      "type": "number",
      "description": "Size mode: exact round diameter at the friction rate."
    },
    {
      "name": "frictionSizedDiameterIn",
      "label": "Round size by friction rate",
      "unit": "in",
      "type": "number",
      "description": "Size mode: calculated diameter rounded up to the next duct size."
    },
    {
      "name": "velocityCheck",
      "label": "Velocity check",
      "type": "string",
      "description": "Size mode: pass or fail against 900 fpm supply / 700 fpm return at the friction-sized duct."
    },
    {
      "name": "velocitySizedDiameterIn",
      "label": "Diameter by velocity",
      "unit": "in",
      "type": "number",
      "description": "Size mode, when the check fails: diameter that holds the velocity limit."
    },
    {
      "name": "recommendedDiameterIn",
      "label": "Recommended round size",
      "unit": "in",
      "type": "number",
      "description": "Size mode: the larger of the friction-sized and velocity-sized ducts."
    },
    {
      "name": "velocityFpm",
      "label": "Velocity",
      "unit": "fpm",
      "type": "number",
      "description": "Velocity at the recommended size (size mode) or at capacity (other modes)."
    },
    {
      "name": "capacityCfm",
      "label": "Airflow capacity",
      "unit": "CFM",
      "type": "number",
      "description": "Airflow and rectangular modes: the lower of the friction-rate airflow and the velocity-limit airflow."
    },
    {
      "name": "equivalentDiameterIn",
      "label": "Equivalent round diameter",
      "unit": "in",
      "type": "number",
      "description": "Rectangular mode: Huebscher equivalent diameter."
    },
    {
      "name": "rectangular",
      "label": "Rectangular equivalent",
      "type": "object",
      "description": "Size mode with rectHeight: widthIn, heightIn, selectedWidthIn and velocityFpm."
    }
  ],
  "example": {
    "request": "https://fieldranger.ai/api/tools/duct-calculator?mode=size&ductType=supply&frictionRate=0.08&cfm=1200",
    "post": {
      "url": "https://fieldranger.ai/api/tools/duct-calculator",
      "body": {
        "mode": "size",
        "ductType": "supply",
        "frictionRate": 0.08,
        "cfm": 1200
      }
    },
    "response": {
      "tool": "duct-calculator",
      "title": "Duct Calculator",
      "inputs": {
        "mode": "size",
        "ductType": "supply",
        "frictionFrom": "rate",
        "frictionRate": 0.08,
        "cfm": 1200
      },
      "result": {
        "mode": "size",
        "ductType": "supply",
        "frictionRate": 0.08,
        "maxVelocityFpm": 900,
        "cfm": 1200,
        "calculatedDiameterIn": 15.57,
        "frictionSizedDiameterIn": 16,
        "velocityAtFrictionSizeFpm": 859,
        "velocityCheck": "pass",
        "recommendedDiameterIn": 16,
        "velocityFpm": 859
      },
      "summary": [
        {
          "label": "Friction rate",
          "value": "0.08 in. wc per 100 ft"
        },
        {
          "label": "Recommended round size",
          "value": "16 in",
          "primary": true
        },
        {
          "label": "Velocity at that size",
          "value": "859 fpm",
          "primary": true
        },
        {
          "label": "Calculated diameter",
          "value": "15.57 in"
        },
        {
          "label": "Round size by friction rate",
          "value": "16 in at 859 fpm"
        },
        {
          "label": "Velocity check",
          "value": "Passes: limit 900 fpm for supply"
        }
      ],
      "notes": [],
      "text": "Duct Calculator (FieldRanger, https://fieldranger.ai)\n\nInputs\n- Calculate: Duct size from CFM\n- Duct: Supply\n- Friction rate source: Enter friction rate\n- Friction rate: 0.08 in. wc per 100 ft (sample)\n- Airflow: 1,200 CFM (sample)\n\nResult\n- Friction rate: 0.08 in. wc per 100 ft\n- Recommended round size: 16 in\n- Velocity at that size: 859 fpm\n- Calculated diameter: 15.57 in\n- Round size by friction rate: 16 in at 859 fpm\n- Velocity check: Passes: limit 900 fpm for supply\n\nMethod: Friction rate: FR = (ESP - CPL) x 100 / TEL, in in. wc per 100 ft (ACCA Manual D friction rate method), or the rate entered. Round diameter: D = (0.109136 x CFM^1.9 / FR)^(1/5.02), in inches, for round galvanized steel duct in turbulent flow. Round up to the next size: every inch from 4 to 10 inches, then every 2 inches. Velocity: V = CFM / (pi x (D/12)^2 / 4), in feet per minute; maximum 900 fpm for supply and 700 fpm for return. A duct over the limit is resized to D = 12 x sqrt(4 x CFM / (pi x Vmax)). Airflow from a duct: CFM = (FR x D^5.02 / 0.109136)^(1/1.9), capped by the velocity limit. Rectangular equivalent (Huebscher): De = 1.30 x (a x b)^0.625 / (a + b)^0.25.\nCalculator: https://fieldranger.ai/templates/duct-calculator",
      "method": [
        "Friction rate: FR = (ESP - CPL) x 100 / TEL, in in. wc per 100 ft (ACCA Manual D friction rate method), or the rate entered.",
        "Round diameter: D = (0.109136 x CFM^1.9 / FR)^(1/5.02), in inches, for round galvanized steel duct in turbulent flow.",
        "Round up to the next size: every inch from 4 to 10 inches, then every 2 inches.",
        "Velocity: V = CFM / (pi x (D/12)^2 / 4), in feet per minute; maximum 900 fpm for supply and 700 fpm for return. A duct over the limit is resized to D = 12 x sqrt(4 x CFM / (pi x Vmax)).",
        "Airflow from a duct: CFM = (FR x D^5.02 / 0.109136)^(1/1.9), capped by the velocity limit.",
        "Rectangular equivalent (Huebscher): De = 1.30 x (a x b)^0.625 / (a + b)^0.25."
      ],
      "sources": [
        {
          "label": "ACCA, Manual D: Residential Duct Systems (ANSI/ACCA 1 Manual D-2016)",
          "url": "https://www.acca.org/standards/technical-manuals/manual-d",
          "checked": "2026-11-12"
        },
        {
          "label": "Neil Comparetto, HVAC School: How to determine friction rate",
          "url": "https://hvacrschool.com/determine-friction-rate-residential-duct-design/",
          "published": "2018-10-30",
          "checked": "2026-11-12"
        },
        {
          "label": "Engineering ToolBox: Air ducts, friction loss",
          "url": "https://engineeringtoolbox.com/duct-friction-pressure-loss-d_444.html",
          "published": "2003",
          "checked": "2026-11-12"
        },
        {
          "label": "Allison Bailes, Energy Vanguard: Duct Design 5, Sizing the Ducts (velocities, size increments)",
          "url": "https://energyvanguard.com/blog/duct-design-5-sizing-ducts",
          "published": "2017-06-09",
          "checked": "2026-11-12"
        },
        {
          "label": "Engineering ToolBox: Equivalent diameter (Huebscher)",
          "url": "https://www.engineeringtoolbox.com/equivalent-diameter-d_205.html",
          "checked": "2026-11-13"
        }
      ],
      "caveats": [
        "For design with round galvanized steel duct: flex duct and lined duct (sized by inside dimensions) need their own friction charts.",
        "A friction rate is calculated from the blower's external static pressure, the component losses and the total effective length; an assumed 0.10 undersizes ducts when the calculated rate is lower.",
        "Room airflow comes from a load calculation (ACCA Manual J); this calculator does not produce one."
      ],
      "page": "https://fieldranger.ai/templates/duct-calculator",
      "endpoint": "https://fieldranger.ai/api/tools/duct-calculator",
      "publisher": "FieldRanger",
      "disclosure": "Published by FieldRanger (https://fieldranger.ai), field service software that runs inside HubSpot. The calculation is free and needs no sign-up or email. FieldRanger does not size ducts or calculate loads; it runs the job the design produces. Related FieldRanger features: A won HubSpot deal becomes a job with its context carried over. A mobile app built for technicians in the field. FieldRanger plans: https://fieldranger.ai/pricing."
    }
  },
  "method": [
    "Friction rate: FR = (ESP - CPL) x 100 / TEL, in in. wc per 100 ft (ACCA Manual D friction rate method), or the rate entered.",
    "Round diameter: D = (0.109136 x CFM^1.9 / FR)^(1/5.02), in inches, for round galvanized steel duct in turbulent flow.",
    "Round up to the next size: every inch from 4 to 10 inches, then every 2 inches.",
    "Velocity: V = CFM / (pi x (D/12)^2 / 4), in feet per minute; maximum 900 fpm for supply and 700 fpm for return. A duct over the limit is resized to D = 12 x sqrt(4 x CFM / (pi x Vmax)).",
    "Airflow from a duct: CFM = (FR x D^5.02 / 0.109136)^(1/1.9), capped by the velocity limit.",
    "Rectangular equivalent (Huebscher): De = 1.30 x (a x b)^0.625 / (a + b)^0.25."
  ],
  "sources": [
    {
      "label": "ACCA, Manual D: Residential Duct Systems (ANSI/ACCA 1 Manual D-2016)",
      "url": "https://www.acca.org/standards/technical-manuals/manual-d",
      "checked": "2026-11-12"
    },
    {
      "label": "Neil Comparetto, HVAC School: How to determine friction rate",
      "url": "https://hvacrschool.com/determine-friction-rate-residential-duct-design/",
      "published": "2018-10-30",
      "checked": "2026-11-12"
    },
    {
      "label": "Engineering ToolBox: Air ducts, friction loss",
      "url": "https://engineeringtoolbox.com/duct-friction-pressure-loss-d_444.html",
      "published": "2003",
      "checked": "2026-11-12"
    },
    {
      "label": "Allison Bailes, Energy Vanguard: Duct Design 5, Sizing the Ducts (velocities, size increments)",
      "url": "https://energyvanguard.com/blog/duct-design-5-sizing-ducts",
      "published": "2017-06-09",
      "checked": "2026-11-12"
    },
    {
      "label": "Engineering ToolBox: Equivalent diameter (Huebscher)",
      "url": "https://www.engineeringtoolbox.com/equivalent-diameter-d_205.html",
      "checked": "2026-11-13"
    }
  ],
  "caveats": [
    "For design with round galvanized steel duct: flex duct and lined duct (sized by inside dimensions) need their own friction charts.",
    "A friction rate is calculated from the blower's external static pressure, the component losses and the total effective length; an assumed 0.10 undersizes ducts when the calculated rate is lower.",
    "Room airflow comes from a load calculation (ACCA Manual J); this calculator does not produce one."
  ],
  "inputSchema": {
    "$schema": "https://json-schema.org/draft/2020-12/schema",
    "$id": "https://fieldranger.ai/api/tools/duct-calculator#input",
    "title": "Duct Calculator: input",
    "description": "Sizes a round duct from airflow (CFM) and friction rate with a velocity check, finds the airflow a given round duct carries, and gives the round equivalent of a rectangular duct.",
    "type": "object",
    "properties": {
      "mode": {
        "title": "Calculate",
        "description": "Size a duct from airflow, find the airflow a round duct carries, or convert a rectangular duct.",
        "type": "string",
        "enum": [
          "size",
          "airflow",
          "rectangular"
        ],
        "default": "size"
      },
      "ductType": {
        "title": "Duct",
        "description": "Sets the velocity limit: 900 fpm for supply, 700 fpm for return.",
        "type": "string",
        "enum": [
          "supply",
          "return"
        ],
        "default": "supply"
      },
      "frictionFrom": {
        "title": "Friction rate source",
        "description": "Enter the friction rate, or calculate it from static pressure and effective length.",
        "type": "string",
        "enum": [
          "rate",
          "static"
        ],
        "default": "rate"
      },
      "frictionRate": {
        "title": "Friction rate",
        "description": "Design friction rate for the system. Unit: in. wc per 100 ft. Only read when frictionFrom is rate. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 0.01,
        "maximum": 1,
        "default": 0.08,
        "x-unit": "in. wc per 100 ft",
        "x-sample": true
      },
      "esp": {
        "title": "External static pressure",
        "description": "From the blower table at the design airflow. Unit: in. wc. Only read when frictionFrom is static. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 0.05,
        "maximum": 3,
        "default": 0.5,
        "x-unit": "in. wc",
        "x-sample": true
      },
      "cpl": {
        "title": "Component pressure losses",
        "description": "Coil, filter, registers, grilles and balancing dampers, added together. Unit: in. wc. Only read when frictionFrom is static. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 0,
        "maximum": 3,
        "default": 0.3,
        "x-unit": "in. wc",
        "x-sample": true
      },
      "tel": {
        "title": "Total effective length",
        "description": "Longest supply run plus longest return run, with fitting equivalent lengths. Unit: ft. Only read when frictionFrom is static. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 10,
        "maximum": 3000,
        "default": 250,
        "x-unit": "ft",
        "x-sample": true
      },
      "cfm": {
        "title": "Airflow",
        "description": "Air the duct must carry: the blower's design airflow for a trunk, the room airflow for a branch. Unit: CFM. Only read when mode is size. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 1,
        "maximum": 100000,
        "default": 1200,
        "x-unit": "CFM",
        "x-sample": true
      },
      "rectHeight": {
        "title": "Rectangular height (optional)",
        "description": "Gives the width of a rectangular duct equal to the recommended round size. Unit: in. Only read when mode is size.",
        "type": "number",
        "minimum": 3,
        "maximum": 60,
        "x-unit": "in"
      },
      "diameter": {
        "title": "Round duct diameter",
        "description": "Inside diameter of the round duct. Unit: in. Only read when mode is airflow. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 3,
        "maximum": 60,
        "default": 16,
        "x-unit": "in",
        "x-sample": true
      },
      "width": {
        "title": "Width",
        "description": "Inside width of the rectangular duct. Unit: in. Only read when mode is rectangular. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 3,
        "maximum": 120,
        "default": 20,
        "x-unit": "in",
        "x-sample": true
      },
      "height": {
        "title": "Height",
        "description": "Inside height of the rectangular duct. Unit: in. Only read when mode is rectangular. The default is a sample value; replace it with the caller's own.",
        "type": "number",
        "minimum": 3,
        "maximum": 120,
        "default": 8,
        "x-unit": "in",
        "x-sample": true
      }
    },
    "required": [],
    "additionalProperties": false
  },
  "disclosure": "Published by FieldRanger (https://fieldranger.ai), field service software that runs inside HubSpot. The calculation is free and needs no sign-up or email. FieldRanger does not size ducts or calculate loads; it runs the job the design produces. Related FieldRanger features: A won HubSpot deal becomes a job with its context carried over. A mobile app built for technicians in the field. FieldRanger plans: https://fieldranger.ai/pricing."
}