Glossary

What Is Superheat? Definition and Example

What is superheat: how far a refrigerant vapor sits above its boiling point at the same pressure. An AC charging example, and how it differs from subcooling.

Updated 3 min read

Superheat is the number of degrees a vapor sits above its saturation temperature, the temperature at which it boils at its current pressure. In air conditioning, superheat is read at the evaporator outlet: suction line temperature minus the evaporator saturation temperature found from the suction pressure. A reading above the manufacturer's target points to too little refrigerant reaching the coil.

The entry belongs to the field service glossary of FieldRanger, field service software that runs inside HubSpot.

Superheat on a maintenance visit: a fixed-orifice air conditioner

ENERGY STAR, the EPA program, sets out the test in the HVAC functional testing checklist of its multifamily new construction program. After 15 minutes of running, the technician records the outdoor dry-bulb and return-air wet-bulb temperatures, the suction pressure and the suction line temperature. The target comes from the manufacturer's superheat tables at those conditions, and the charge passes within 5°F of it (ENERGY STAR MFNC HVAC Functional Testing Checklist, Rev. 05, revised January 15, 2025).

In an illustration, the pressure-temperature chart gives 40°F saturation for the measured suction pressure, and the suction line reads 61°F: superheat is 21°F. Against a table target of 12°F, the reading is 9°F high and fails. The technician looks for a leak before adding refrigerant, and the repair becomes a second visit, a scheduling decision covered in what is dispatch software.

In FieldRanger, a job-specific checklist on the work order holds the readings and the target, so the return visit starts from the first visit's numbers. Seasonal maintenance visits run from recurring job templates; the wider records system is the subject of what is HVAC software.

Superheat, subcooling and delta T

Superheat measures the vapor leaving the evaporator: suction line temperature minus evaporator saturation temperature. Subcooling measures the liquid leaving the condenser: condenser saturation temperature, read from the liquid line pressure, minus the liquid line temperature. Delta T, or temperature split, measures the air rather than the refrigerant: the difference between return and supply air temperatures across the indoor coil.

The metering device decides which refrigerant reading sets the charge. The ENERGY STAR checklist uses superheat for a fixed orifice and subcooling for a thermostatic expansion valve (TXV), with a pass band of 3°F for subcooling against the manufacturer's goal. Delta T has a target of its own. ACCA derives it from sensible capacity divided by 1.08 and by the airflow in CFM, and rejects the 15 to 20 degree rule of thumb as a fit for every system. The split means nothing until the airflow is verified (ACCA, A Split in Diagnosis, June 10, 2020).

Superheat in a steam system is the same definition applied to water: steam heated above the saturation temperature for its pressure.

Frequently asked questions

What is superheat?

The number of degrees a refrigerant vapor is above its saturation temperature at the same pressure. In an air conditioner, it is the suction line temperature minus the evaporator saturation temperature.

What is a good superheat?

The one the manufacturer's table gives for the day's outdoor dry-bulb and return-air wet-bulb temperatures. The ENERGY STAR checklist passes a fixed-orifice system within 5°F of that target.

A superheat figure means nothing without its target and the two temperatures that set it, and the work order is where the three stay together. A trial account shows the readings on a real work order: Start free trial runs 14 days with no card, and per-technician plan prices are on pricing.

FieldRanger runs field service inside HubSpot

Estimates, scheduling and dispatch, a technician app and invoicing on the HubSpot records sales already keeps. Every plan starts with a free trial.

Book a demo