Glossary

What Does VAV Stand For in HVAC? Definition and Example

What does VAV stand for in HVAC: variable air volume, a system that varies each zone's airflow with its load. Box parts, a reheat calculation and VAV vs CAV.

Updated 3 min read

In HVAC, VAV stands for variable air volume: a system in which a central fan supplies conditioned air and a terminal unit at each zone, the VAV box, varies how much of that air the zone receives in response to its thermostat. The air handler conditions the air; the box sets each zone's share of it.

This definition is one of the HVAC entries in the field service glossary from FieldRanger, whose HVAC software runs inside HubSpot.

VAV system parts: air handler, terminal and controls

The air handler holds the supply fan. AAON describes a VAV system as one that adjusts "the amount of air delivered by a fan" to heat or cool a space "based on demand", with the fan on a variable frequency drive that follows the zone dampers (AAON, checked November 2026).

Titus describes the basic single duct terminal as a casing, a damper, an actuator and controls that, on a thermostat's signal, "varies the airflow through a single duct handling hot or cold air" (Titus, Terminal Units Engineering Guidelines, PDF dated March 2019). A single duct terminal with reheat adds a hot water or electric coil. A fan-powered terminal adds a fan that recirculates air from the ceiling plenum.

The controls hold a maximum and a minimum airflow for each box; pressure independent control, in the Titus guide, uses a velocity sensor to hold the flow between them whatever the duct pressure. AAON notes that the box keeps a minimum airflow for ventilation, and that minimum is also the flow a reheat coil heats.

Sample VAV calculation: minimum flow and reheat

The Titus guide gives the heating flow as "typically 30 - 50% of the cooling cfm" and sizes the room and the coil with the 1.085 air factor: heat equals 1.085 × temperature difference × cfm.

Reheat for one VAV box, illustrative inputs
Input or stepValueWorking
Maximum cooling airflow800 CFMBox schedule
Heating airflow240 CFM30% of 800, the low end of the Titus range
Zone heating load3,500 Btu/hLoad calculation
Room setpoint70°FDesign condition
Primary air temperature55°FAir handler supply
Air entering the room83.4°F70 + 3,500 ÷ (1.085 × 240)
Reheat coil outputabout 7,400 Btu/h1.085 × (83.4 − 55) × 240

The air enters the room 13.4°F above setpoint, inside the guide's limit of 15°F between room and diffuser discharge. About 3,900 Btu/h of the coil's output only lifts the primary air from 55°F to room temperature; the other 3,500 Btu/h heats the zone. Each extra 10 CFM of minimum flow adds about 160 Btu/h to the first figure, 1.085 × 10 × 15.

A service call on a VAV box compares both settings with the schedule, then checks the actuator and reheat valve; in FieldRanger, a recurring job template can hold that seasonal check.

VAV, constant air volume and dual duct

A VAV system varies the volume of air each zone receives. A constant air volume (CAV) system delivers a constant volume and meets part load by shutting off or changing the supply air temperature, in AAON's comparison. A dual duct system supplies hot and cold air in two ducts, and its terminal modulates the two streams, per the Titus guide. All three move air measured in cubic feet per minute, the unit defined under what does cfm stand for in HVAC.

Frequently asked questions

What does VAV stand for in HVAC?

Variable air volume: a system in which a central fan supplies conditioned air and a VAV box at each zone varies the airflow to that zone in response to its thermostat.

What is a VAV box?

The terminal unit that controls one zone's airflow: a casing, a damper, an actuator and controls, with a heating coil or a fan added in reheat and fan-powered types.

What is the difference between VAV and CAV?

A VAV system varies the air volume each zone receives as its load changes. A CAV system delivers a constant volume and meets part load by changing the supply temperature or shutting off.

Each VAV box carries two airflow settings, and the lower one sets how much reheat the building pays for. Start free trial gives an HVAC service team 14 days, card-free, to build its seasonal VAV check as a recurring job; per-technician plan prices are on pricing.