Guide

Commercial HVAC Service Agreement:Equipment Schedule, ASHRAE/ACCA 180 Task Frequencies, Response Times, Refrigerant Rules and Per-Ton Pricing

Commercial HVAC service agreement terms: equipment schedule, ASHRAE/ACCA 180 task frequencies, filters and belts, response times, EPA leak rules and pricing.

By Published Updated

13 min read

A commercial HVAC service agreement is a contract under which a contractor inspects and maintains a building's heating, cooling and ventilation equipment on a schedule for a fixed annual price, with stated response times for breakdowns. It lists every unit, sets the frequency of each task, says who keeps refrigerant records, and prices work outside its scope.

An agreement written without those parts fails at points that can be named in advance. The price was set per visit before anyone counted the rooftop units; "filters as needed" leaves the filter bill open; a four-hour response time never says when the four hours start; an older chiller holding more than 50 pounds of R-22 leaks, and nobody agreed who calculates the leak rate. FieldRanger makes HVAC software that runs inside HubSpot. This guide covers maintenance and service agreements, the equipment schedule, task frequencies under ANSI/ASHRAE/ACCA Standard 180, filters and belts, response times, federal refrigerant rules for larger systems, pricing per ton and per unit, the service call price, a sample agreement for an office building, a checklist and the visit record. The clause-by-clause form, with a filled residential example, is the HVAC service agreement template.

Four definitions apply throughout. Standard 180 is ANSI/ASHRAE/ACCA Standard 180-2018, Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems. A full charge is the amount of refrigerant an appliance holds to run normally, the figure against which EPA's size thresholds are measured. Comfort cooling is air conditioning for people, as distinct from commercial refrigeration and industrial process cooling. A ton of cooling capacity is 12,000 BTU per hour.

Commercial HVAC maintenance agreement and service agreement compared

A commercial HVAC maintenance agreement covers scheduled inspection and maintenance: the visits, the tasks on each and the consumables. A commercial HVAC service agreement adds the work between visits: response to breakdowns within stated times, and repair labor included or at a contract rate. The buyer's need decides the form. A property manager who wants equipment kept to a standard buys maintenance; one who wants a single number to call when a unit fails buys service.

Commercial HVAC maintenance and service agreements compared
TermMaintenance agreementService agreement
Scheduled visits and tasksIncludedIncluded
Filters and beltsIncluded or listedIncluded or listed
Breakdown response timeNot statedStated by priority
Repair laborQuoted job by jobIncluded or at a contract rate
Price basisPer unit, per ton or per visitThe same, plus a coverage charge

Equipment schedule: units, capacity and refrigerant charge

The agreement's first exhibit is the equipment schedule, and Standard 180 sets its minimum content. The standard requires an inventory of the HVAC systems and equipment that affect thermal comfort, energy efficiency and indoor air quality. The inventory lists manufacturers' information, location, capacity and a maintenance program identifier, and each piece of equipment in it is uniquely identified (ANSI/ASHRAE/ACCA Standard 180-2018, public preview, sections 3 and 4.3.1, checked November 12, 2026).

For pricing and compliance, three more columns earn their place: refrigerant type, full charge in pounds, and filter size and count per unit. The charge column decides which EPA rules reach the unit, and the filter column decides the consumables bill. A schedule built from a walk of the roof and the mechanical rooms, not from the property manager's list, catches the unit nobody mentioned. The agreement also states the insurance the contractor carries and the certificate it delivers to the owner; coverage choices are covered in best commercial insurance for small HVAC business.

Task frequencies under ANSI/ASHRAE/ACCA Standard 180

Standard 180 states its purpose as establishing "minimum HVAC inspection and maintenance requirements that preserve a system's ability to achieve acceptable thermal comfort, energy efficiency, and indoor air quality in commercial buildings." It does not apply to single-family houses, to multifamily structures of three or fewer stories above grade, or to equipment that primarily serves industrial, manufacturing or commercial processes. The building owner is responsible for meeting it and may designate other parties that are authorized and contractually obligated to fulfill that responsibility, which is the role a service agreement gives the contractor.

Section 5 of the 2018 edition sets out tasks in 25 equipment tables, from air distribution systems and air handlers through rooftop units (Table 5-22) to water-source heat pumps, and states that the baseline frequencies are "the minimum required for compliance." The public preview shows the first two tables in full.

Selected Standard 180-2018 tasks and minimum frequencies (Tables 5-1 and 5-2, public preview)
EquipmentTaskMinimum frequency
Air handlerCheck filters for particulate accumulation; clean or replace as neededQuarterly
Air handlerCheck drain pan, drain line and coil for biological growth; cleanQuarterly
Air handlerCheck P-trap; prime as neededQuarterly
Air handlerCheck fan-belt tension, belt wear and sheave alignmentSemiannually
Air handlerCheck variable-frequency drive; clean housing, tighten connectionsSemiannually
Air handlerCheck controls; clean, lubricate, adjustSemiannually
Air distributionInspect grilles, registers and diffusers; check dampersSemiannually
Air distributionInspect exposed duct insulation and lined duct near moisture sourcesAnnually

The visit count follows from the shortest interval. Equipment with quarterly tasks needs four visits a year; semiannual tasks fall on two of them and annual tasks on one. The rooftop unit, chiller, boiler and cooling tower tables sit in the purchased standard, not the preview, and an agreement covering that equipment takes its frequencies from them.

The frequencies move with the findings. Unacceptable conditions on two successive inspections require a review of whether the frequency should increase, and acceptable results on three successive inspections require a review for chances to reduce it. The standard does not supersede a manufacturer's warranty terms. The owner and the contractor hold at least two formal review meetings, one at the beginning of the performance period and one at its end. A task-by-task record of each visit is what makes those reviews possible, and the HVAC maintenance checklist is one form for it.

Filters and belts in the agreement price

Filters and belts are the consumables the standard checks on its shortest intervals: filters quarterly and belts semiannually. "Clean or replace as needed" is the standard's maintenance task for filters, which leaves the quantity open, and the agreement closes it. Each unit's filter size, rating and count goes into the schedule with the number of changes the price includes per year. Belts are listed by size, with replacement included at a stated frequency or billed as found.

The choice moves cost between the parties. Filters included at four changes a year put the risk of a dusty site on the contractor; filters billed per change put it on the owner and turn every visit into an invoice. Belts billed as found give the contractor no reason to replace a worn belt before it fails, while a scheduled replacement inside the price lines the incentive up with the semiannual belt check.

Response times and the service clock

A response time is a promise measured from a moment the agreement has to name. The clock starts when a call reaches a stated channel, such as the dispatch line or a service portal, not when a technician is assigned. The agreement defines priorities by consequence, for example loss of cooling to a server room or a whole floor as priority one and a single noisy unit as priority three. Each priority gets one response time for business hours and another for after hours, and the after-hours labor rate is stated. Arrival is recorded by the technician's clock-in on site, which turns a disputed response into a lookup.

Credits for missed response times belong in a service level agreement attached to the contract. The service level agreement template drafts the clock, the credit and the monthly report.

Refrigerant compliance under EPA Section 608 and the AIM Act

Two federal leak repair regimes reach commercial equipment, divided by refrigerant. Under Clean Air Act Section 608, owners or operators must take corrective action when an appliance with a full charge of 50 or more pounds of ozone-depleting refrigerant leaks above the trigger rate: 10 percent a year for comfort cooling, 20 percent for commercial refrigeration and 30 percent for industrial process refrigeration. Repairs are due within 30 days of discovery, or 120 days where an industrial process shutdown is required, and initial and follow-up verification tests follow the repair (EPA, Stationary Refrigeration Leak Repair Requirements, updated December 8, 2025).

Since January 1, 2026, the AIM Act Emissions Reduction and Reclamation rule has applied parallel requirements to appliances with 15 pounds or more of a refrigerant containing an HFC, or of a substitute with a global warming potential above 53. The thresholds are the same 10, 20 and 30 percent. A leak rate is calculated each time refrigerant is added, and leaks above the threshold are repaired within 30 days of that addition. An appliance that leaks 125 percent or more of its full charge in a calendar year is reported to EPA by March 1 of the following year, and records are kept for three years. Appliances in the residential and light commercial air conditioning and heat pumps subsector, which EPA describes as equipment for cooling individual rooms, single-family homes and small commercial buildings, are exempt. Chillers and certain variable refrigerant flow systems belong to their own subsectors and are covered (EPA, AIM Act Leak Repair Requirements fact sheet, January 2026).

Federal leak repair rules for commercial HVAC equipment (checked November 12, 2026)
TermCAA Section 608AIM Act ER&R rule
RefrigerantOzone-depleting: CFCs and HCFCs such as R-22HFCs, or substitutes with a GWP above 53
Full charge50 pounds or more15 pounds or more
Comfort cooling threshold10% a year10% a year
Repair deadline30 days from discovery30 days from the refrigerant addition
ExemptionNone at 50 pounds or moreResidential and light commercial air conditioning and heat pumps

The agreement assigns the work these rules create. The technician who adds refrigerant records the amount and calculates the leak rate; the owner or operator, who carries the legal obligation, keeps the records; and the agreement says whether leak repair and verification tests fall inside the price or are quoted. Only a certified technician opens the circuit. Type II certification covers high- and very high-pressure appliances other than small appliances and motor vehicle air conditioners, Type III covers low-pressure appliances, and apprentices are exempt only while closely and continually supervised by a certified technician (EPA, Section 608 Technician Certification Requirements, updated July 15, 2026).

Commercial HVAC pricing per ton and per unit

Commercial agreements are priced per ton, per unit or per visit. Per-ton pricing is quick to quote from a list of nameplates, and it misprices any building whose tonnage is split across many small units, since inspection time, filters and belts scale with the number of units rather than with tons. Per-unit pricing follows the work. A per-visit figure is a presentation of either one, divided by the visits the schedule requires.

Sample agreement: four rooftop units on a two-story office building

The agreement below is a sample for a hypothetical two-story office building with four packaged rooftop units of 7.5 tons each, 30 tons in all. Each unit holds a sample 11 pounds of R-410A, below the AIM Act's 15-pound threshold, which the equipment schedule records for exactly that reason. The wage, compensation ratio and mileage rate are published figures; hours, miles, filter and belt prices, overhead and margin are sample inputs.

Labor uses the BLS median wage for heating, air conditioning and refrigeration mechanics and installers, $29.33 an hour in May 2025 (BLS Occupational Outlook Handbook, modified October 29, 2026), divided by 0.700, the wage share of private-industry compensation in June 2026 (BLS Employer Costs for Employee Compensation, released September 9, 2026), for a loaded $41.90 an hour. Vehicle cost uses the IRS business rate of 76 cents a mile from July 1, 2026 (IRS standard mileage rates, updated July 28, 2026).

Sample annual price for four 7.5-ton rooftop units on quarterly visits (published rates and sample inputs)
LineCalculationAmount
Technician hours4 units × 6.0 sample hours a year (1.0 at each quarterly visit, 0.5 more at two semiannual visits, 1.0 more for the annual coil cleaning), plus 4 visits × 1.0 hour of travel28.0 hours
Labor28.0 × $41.90$1,173.20
Vehicle4 visits × 30 sample miles × $0.76$91.20
Filters4 units × 4 filters × 4 changes × $9.00 sample$576.00
Belts4 units × 1 belt a year × $18.00 sample$72.00
Overhead28.0 hours × $25.00 sample$700.00
Annual costSum$2,612.40
Annual price at a 25% margin$2,612.40 ÷ 0.75$3,483.20
Per ton$3,483.20 ÷ 30$116.11
Per unit$3,483.20 ÷ 4$870.80

The per-ton figure is a result of the table, not an input to it. With the same 30 tons in eight 3.75-ton units, the same hours per unit and two filters each, the year costs $4,290.00 and prices at $5,720.00, or $190.67 a ton. A per-ton rate of $116.11 copied from the four-unit building would bring in $3,483.30 on the eight-unit building, $2,236.70 short of its price. How the agreement is sold once it is priced is covered in how to sell HVAC service contracts.

HVAC service call price for work outside the agreement

The agreement also fixes the price of calls it does not cover, from the same inputs. In the sample, an hour of technician time costs $41.90 of loaded labor plus $25.00 of overhead, $66.90 in all. A call with a sample 1.0 hour on site and 0.5 hour of travel, plus 30 miles at the IRS rate, costs $123.15 ($66.90 × 1.5 + $22.80) and prices at $164.20 at a 25 percent margin.

The agreement states that figure as the first-hour charge, with the rate for each further hour, the after-hours multiplier and any discount agreement customers receive. A call outside scope then produces an invoice the property manager has already seen in the contract, instead of a negotiation.

Commercial HVAC service agreement checklist

  1. Walk the roof and mechanical rooms and list every unit with tag, location, capacity, refrigerant type and full charge.
  2. Mark each unit's leak repair regime: Section 608 at 50 pounds of ozone-depleting refrigerant, the AIM Act rule at 15 pounds of HFC, or neither.
  3. Take task frequencies from the Standard 180 table for each equipment type, or from the manufacturer where it requires more.
  4. Write filter size, rating, count and changes per year for each unit into the schedule.
  5. List belts by size and state whether replacement is included.
  6. Define priorities, response times, the event that starts the clock and the after-hours rate.
  7. Price per unit from hours, filters and belts, and show the per-ton figure only as a result.
  8. State the service call price for work outside scope.
  9. Put the beginning and end review meetings with the owner on the calendar.
  10. Verify after the first quarter: each unit's visit record against the schedule, and hours logged against hours priced.

Agreement visits as recurring jobs in FieldRanger

Each line of the schedule becomes a visit on a date. FieldRanger creates recurring job templates for maintenance contracts and repeat service calls, so quarterly visits come from the agreement instead of being typed in one by one; the recurring service scheduling software page shows the templates. Dispatchers assign and reschedule visits by dragging them on the calendar, and FieldRanger builds each technician's route for the day automatically. Technicians clock in and out with time logged against each job, which is the arrival record behind a response time and the hours record behind the price. Job-specific checklists hold the Standard 180 tasks for each unit, and before and after photos attach to the work order.

The invoice for out-of-scope work is generated from the completed work order, QuickBooks syncs invoices and payments, and revenue reports show job revenue and margin by customer or service type, so an agreement priced too low per ton shows up in its own margin line. Renewal estimates are built from the HubSpot deal or contact record, and PandaDoc sends agreements for signature. Pricing lists the plans; Start free trial runs 14 days without a card.

Frequently asked questions

What does a commercial HVAC maintenance agreement include?

An equipment schedule, the inspection and maintenance tasks for each unit at stated frequencies, the filters and belts included, and the price. A service agreement adds breakdown response times and repair terms.

How frequently should commercial HVAC equipment be serviced?

ANSI/ASHRAE/ACCA Standard 180-2018 sets quarterly minimums for air handler filter, drain pan and P-trap checks and semiannual minimums for belts, drives and controls, so equipment maintained to it needs at least four visits a year.

How much does a commercial HVAC service agreement cost?

It is priced from hours, filters, belts, travel and overhead per unit. In the sample, four 7.5-ton rooftop units on quarterly visits price at $3,483.20 a year, or $116.11 a ton, at a 25% margin.

How is an HVAC service call price set?

From loaded labor, overhead, travel and margin. The sample call of 1.5 hours and 30 miles costs $123.15 and prices at $164.20.

Who keeps refrigerant leak records on a commercial system?

The owner or operator carries the obligation under EPA's rules for appliances with 50 pounds or more of ozone-depleting refrigerant and, since January 1, 2026, 15 pounds or more of HFC refrigerant. The agreement assigns the leak rate calculation to the technician who adds refrigerant.

Thirty tons of rooftop cooling prices at $3,483.20 a year in four units and needs $5,720.00 in eight, and only the equipment schedule tells the contractor which building it is signing.