A construction roofing siding and windows checklist is the exterior contractor's record that the building envelope sheds water before each layer is covered: roof underlayment, ice dam protection, shingle fastening and valley flashing, the water-resistive barrier, window flashing, wall flashing and siding penetrations. The filled example inspects a new two-story house in Appleton, Wisconsin.
FieldRanger, the roofing contractor software that runs inside HubSpot, keeps this checklist among its free field service templates. The page offers the tables as a free .xlsx download with no sign-up: a Template sheet with every check and a result column, and a Sample sheet with the filled inspection. Roof and wall rows cite Wisconsin's Uniform Dwelling Code, chapter SPS 321 (Register November 2024 No. 827). Window rows follow Marvin's published flashing instruction, document 19913776, dated April 29, 2026.
Envelope checks in the order work is covered
The checklist runs in the order the work disappears. A water-resistive barrier lap cannot be inspected once siding covers it, and a window's sill pan cannot be seen once the window sits on it. Each row is therefore checked at its own hold point, before the next trade covers it, and the form records the time and the inspector for each group.
Wisconsin writes one hold point into the code. Under SPS 321.24(2), "wall cavity insulation may not be installed until a water-resistant covering is in place over the wall cavity and windows, doors and a roof with at least underlayment are installed" (Wisconsin Administrative Code, chapter SPS 321, Register November 2024 No. 827, read November 13, 2026). The envelope checklist is the evidence the insulation crew may start.
This checklist covers water, not people. The job site safety checklist covers fall protection, ladders and the other OSHA construction items for the crew doing the same work.
Roof items under SPS 321.28
| Item | Rule | What the inspector records |
|---|---|---|
| Drainage and fasteners | 321.28(1): roofs "designed and constructed to assure drainage of water"; all fasteners corrosion resistant | Fastener type from the box label |
| Underlayment | 321.28(2): number 15 asphalt-impregnated felt or equivalent, or Type I material showing no water transmission under ASTM D 226 or D 4869; D 1970 materials meet the section by note | Product name and the standard on its label |
| Ice dam protection, where required | 321.28(4)(a): shingled or shake roofs over a heated area of a dwelling or attached garage, with a slope of 4:12 or less; sheet metal or a product labeled ASTM D 1970 | Slope of each roof plane, and whether the rule applies |
| Ice dam protection, extent | 321.28(4)(b): at least 30 inches up the slope from the roof edge and at least 12 inches up the slope beyond the inner face of the exterior wall | Required width computed for each plane; width installed |
| Shingle label and instructions | 321.28(3)(a)2 and 3: package labeled to the applicable ASTM standard; shingles installed to the manufacturer's recommendations | Shingle product and the instruction sheet on site |
| Fasteners per shingle | 321.28(3)(a)4: at least 4 per strip shingle or 2 per interlocking shingle, unless the manufacturer has other specifications | Nail count at three lifted shingles per plane |
| Head lap | 321.28(3)(a)5: at least 2 inches unless the manufacturer specifies otherwise | Measured head lap |
| Flashing locations | 321.28(7)(a): at chimneys, in all valleys and around all roof openings | Each opening and valley, flashed or not |
| Open valleys | 321.28(7)(b): No. 28 gauge corrosion-resistant metal or 50-pound roll roofing, 16 inches wide, over No. 15 underlayment; sections lapped at least 4 inches | Valley material, width and laps |
| Closed valleys | 321.28(7)(c): 50-pound roofing at least 20 inches wide over No. 15 underlayment, or a product labeled ASTM D1970 | Valley lining product |
| Chimney | 321.28(7)(d): flashed and counter-flashed at least 6 inches high; cricket where the upper side is more than 30 inches wide | Flashing height; chimney width and cricket |
| Reroofing | 321.28(6): no new covering over wet or deteriorated roofing, over shake, slate, clay or cement tile, or over two or more existing layers | Layers found at tear-off, on alterations |
The ice dam rule reaches only low-slope planes, and the slope column decides it. A 7:12 main roof falls outside 321.28(4)(a), while a 4:12 roof over a heated room falls inside it. The extent is two tests, and on a deep eave the 12-inch test governs. Its width is the overhang plus the wall thickness, converted to a length along the slope, plus 12 inches. A note under SPS 321.28(3) adds that SPS 320.04(2) applies these roofing provisions to an alteration of any dwelling the code regulates. The same rows therefore serve a reroof on a UDC house.
Wall flashing and water-resistive barrier items under SPS 321.24
| Item | Rule | What the inspector records |
|---|---|---|
| Barrier coverage | 321.24(4)(a)1: a water-resistive barrier on wood or metal frame walls "from the highest point to the bottom of the permanent weather-resistant covering" | Barrier product; coverage at gables and the bottom edge |
| Barrier performance | 321.24(4)(c)1: polymer house wraps rated 5 perms or higher under ASTM E96, with a water-resistance rating under ASTM D779, AATCC 127 or CCMC 07102 | Product data sheet on site |
| Barrier laps | 321.24(4)(d): horizontal seams lapped at least 2 inches, upper over lower; vertical seams at least 6 inches; tears patched the same way | Shortest lap found on each wall |
| Small penetrations | 321.24(4)(e)2: 5 square inches or less, within the rule's annular-space limit, sealed with caulk or similar | Each penetration and its seal |
| Large penetrations | 321.24(4)(e)3: over 5 square inches, flashed under subsection (3) | Each penetration and its flashing |
| Flashing joints | 321.24(3)(c): vertical joints lapped at least 6 inches and sealed; horizontal joints at least 2 inches and sealed unless the flashing manufacturer specifies otherwise; exterior-grade compatible sealant | Laps at each flashing joint |
| Window and door heads | 321.24(3)(d)1: flashing at the top of all exterior door and window openings, unless self-flashing windows provide at least one inch of flashing around the opening, corners included | Head flashing at each opening |
| Projecting trim | 321.24(3)(d)4: flashing continuously above all projecting wood trim | Each band board and trim head |
| Porches, decks and stairs | 321.24(3)(d)5: where they attach to a wood-frame wall or floor | Ledger flashing |
| Wall and roof intersections | 321.24(3)(d)6 and (e): flashing at intersections; rake-wall flashing extends at least one-half inch down the roof past the head-wall flashing | Step and head-wall flashing at each dormer |
| Roof eave against a sidewall | 321.24(3)(f): the end of the roof flashing installed so that it "diverts water away from the sidewall and onto the roof or into the gutter" | Diverter, or kick-out, at each eave-sidewall corner |
| Elevated door openings | 321.24(3)(d)8: flashing along the bottom of door openings above grade | Sill flashing at each elevated door |
Window installation items from Marvin's flashing instructions
Window rows come from the manufacturer, and the checklist names the instruction it follows. Marvin's "Window Rough Opening Prep and Flashing, Method A1-Membrane Drainage System" covers new wood-frame construction. The weather resistive barrier "is to be applied prior to window installation", and head flashing goes over the face of the mounting flange (Marvin, document 19913776, dated April 29, 2026). It states plainly: "Nailing fin is not designed to be a weatherproof flashing."
| Step | Instruction | What the inspector records |
|---|---|---|
| Barrier cut | Horizontal cuts across the top and bottom of the opening, a vertical cut down the center, and 45-degree cuts away from the top corners; at the bottom corners, trim up about 2 inches, then cut about 3 1/2 inches horizontally | Cut pattern; head flap tacked up |
| Sill pan | A Type III flexible membrane sill pan, with an optional sloped sill wedge | Pan in place before the unit |
| Side flaps | Wrapped to the interior and stapled about 1 1/2 inches from the interior edge, leaving 1 to 1 1/2 inches of bare wood, taped with seam seal tape | Flaps wrapped and taped |
| Shims | Plastic or composite shims at the ends and middle of the opening | Shim material and positions |
| Corner patches | A 2-inch by 4-inch strip of flashing at 45 degrees across each corner of the fin | Four patches per unit |
| Drip cap | Factory vinyl drip cap about 1/8 inch past each side, or a rigid head flashing; a bead of sealant under it | Drip cap, extension and sealant |
| Jamb flashing | Vertical strips of adhesive flashing tape lapped onto the unit and out over the barrier | Jamb tape laps |
| Head flashing | Adhesive membrane over the head jamb and sheathing, extending over the jamb flashing, top edge taped | Head over jambs, top edge taped |
| Head flap | Barrier folded down over the head flashing; seam seal tape over the diagonal cuts, lapping onto the unit or casing | Flap down and diagonals taped |
| Interior air seal | Backer rod and sealant at the interior plane, with loose-fill fiberglass or low-expansion closed-cell foam in the cavity | Air seal continuous |
| Exterior sealant | After siding: a bead between finish and frame along the sides and 1 to 2 inches at the ends on top of the drip cap; sealant ASTM C920 Grade NS Class 25 | Product and the C920 grade on the tube |
The instruction sets no fastener spacing for the fin. Spacing comes from the window unit's own installation instruction, which the checklist cites separately. Marvin also states that "Regional standard practices, environmental conditions, and codes may vary and supersede the procedures contained within." The head-flashing row therefore sits beside SPS 321.24(3)(d)1 rather than replacing it.
Header and sign-off fields
| Field | What goes in it |
|---|---|
| Company and job | Contractor name, job number and site address |
| Stage | Roof dry-in, barrier and windows, siding, or final |
| Date and inspector | Date, inspector's name and the time each group of rows was checked |
| Weather | Rain since the last inspection and temperature, for tape and sealant application limits |
| Roof planes | Each plane with its slope and whether it covers heated space |
| Work by others | Trades on site whose work penetrates the envelope: plumbing vents, dryer and bath fan ducts, electrical |
| Holds | Each row that stopped the next trade, the correction and the release time |
| Photos | Each hold, and one photo per wall and roof plane before it is covered |
| Sign-off | Inspector and contractor's lead, with date and time |
Filled checklist: new two-story house in Appleton, Wisconsin
The house has a 7:12 main roof, a one-story rear family room under a 4:12 roof, a 3:12 roof over an unheated front porch, and an attached garage whose 6:12 roof meets the house sidewall. It has 14 flanged windows and fiber cement lap siding. The company, house, products and findings are samples; the rules are SPS 321 and Marvin 19913776.
| Field | Sample entry |
|---|---|
| Company and job | Example Envelope Contractors LLC · job 26-208 · 1900 Example Lane, Appleton, WI 54913 |
| Stage | Roof dry-in, barrier and windows |
| Date and inspector | Tuesday, November 10, 2026 · J. Lindqvist, roofing at 8:10 AM, walls and windows at 10:40 AM |
| Weather | No rain since November 7 · 41°F at 10:40 AM |
| Roof planes | Main 7:12 over heated space · family room 4:12 over heated space, 18-inch overhang, 6.5-inch wall · porch 3:12 over unheated porch · garage 6:12 |
| Work by others | Plumber: two roof vents · HVAC: 4-inch dryer duct, west wall · plumber: 7/8-inch PEX to hose bib, south wall |
| Row | Result | Entry |
|---|---|---|
| Underlayment | OK | Synthetic underlayment, data sheet citing the ASTM D 4869 water transmission test (sample product); laps per its instruction |
| Ice dam, applies | Recorded | Required on the family room plane only: 4:12 over heated space. Main 7:12 and garage 6:12 are over the slope limit; the porch is unheated |
| Ice dam, extent | Corrected | Family room: (18 + 6.5) in × 1.0541 = 25.83 in along the slope, plus 12 in = 37.83 in required, beyond the 30-in minimum. One 36-in course was down; a second course lapped over it |
| Ice dam, main roof | OK | One 36-in course at the eaves, as the contract specifies; not required by 321.28(4) at 7:12 |
| Fasteners per shingle | OK | 6 nails at three lifted shingles per plane, the count in the shingle manufacturer's instruction for this job |
| Head lap | OK | Within the manufacturer's exposure |
| Flashing locations | OK | Two plumbing vents booted; closed valley at the garage lined with ASTM D1970 membrane; no chimney |
| Barrier laps | Corrected | North wall, northeast corner: vertical lap 4 in; a strip added for a 6-in lap and taped |
| Small penetrations | OK | 7/8-in PEX, 0.60 sq in: sealed |
| Large penetrations | Hold | Dryer duct, 4-in round, 12.57 sq in: over 5 sq in, so flashed under 321.24(3); flashing block not yet on site. Siding held on the west wall |
| Window W-6, head flap | Corrected | Head flap taped down before the head membrane went on; tape cut, flap lifted, membrane installed over the jamb tape, flap folded down and diagonals taped |
| Windows, all others | OK | 13 units: pan, corner patches, jamb then head laps, flap down |
| Eave against sidewall | Hold | Garage roof meets the house's east wall with no diverter; kick-out to be installed before siding on that wall |
| During-construction rule | Hold | Patio door in the south wall not delivered; under 321.24(2), cavity insulation in that wall waits for the door, and siding waits for its flashing |
| Sign-off | Partial release | Siding released on the north wall, 11:55 AM; south, west and east walls held |
Two holds share a pattern: a small item, and a siding crew ready to cover it. The dryer duct is 12.57 square inches, so a bead of caulk does not satisfy 321.24(4)(e). The kick-out is the diverter 321.24(3)(f) requires at the garage eave. Both are fixed with the barrier exposed, before siding covers the wall.
Checklist procedure from dry-in to final caulk
- Record each roof plane's slope and whether it covers heated space, then decide the ice dam rows before the first course of membrane goes down.
- Compute the ice dam width for every plane the rule reaches, as overhang plus wall thickness along the slope plus 12 inches, and compare it with 30 inches.
- Check underlayment, valleys, roof openings and nail counts plane by plane before shingles cover each one.
- Walk every wall for barrier coverage and laps, then measure every penetration and mark it sealed or flashed.
- Check each window against the manufacturer's steps in order, before the next step covers the last.
- Check flashing at heads, trim, ledgers, roof-wall intersections and each eave that meets a sidewall.
- Release walls one by one, and hold any wall with an open row, recording the reason and the correction needed.
- At final, confirm each held row has a release time and a photo, and that exterior sealant at the windows carries the ASTM C920 grade.
Work order software and the envelope checklist
On paper, the checklist is signed on the tailgate and the photos that prove its rows sit in someone's phone.
In FieldRanger, custom checklists carry job-specific rows for quality and compliance, and before and after photos attach to the work order. The work order puts job details, customer information and instructions on the assigned technician's phone, and the customer signs on site as proof of completion. Job status is visible to dispatchers in real time, and job completions and notes are logged to the HubSpot timeline. Photos taken on the job sync to the customer's HubSpot record. The work order software page describes the work order those rows ride on.
Each day is its own job in FieldRanger, so an envelope inspection on Tuesday and the siding release on Friday are two jobs; multi-day jobs are not built. The dispatcher reads each failed row and schedules the siding job for that wall only after the row is released. The roofing estimate template prices the ice dam courses and flashing these rows inspect, and the roofing invoice template bills them.
Fill it in here, or download the spreadsheet
The form below is the same template: totals calculate as you type, with the spreadsheet's own formulas, and your entries stay in this browser. Download it filled in, print it or save it as a PDF, or take the blank file.
Frequently asked questions
What is on a construction roofing, siding and windows checklist?
Roof underlayment, ice dam protection, shingle fasteners and head lap, valley and roof-opening flashing, the water-resistive barrier and its laps, wall penetrations, window flashing in the manufacturer's order, head and trim flashing, and the diverter where a roof eave meets a sidewall, each checked before the next layer covers it.
Is ice and water shield required on roofs in Wisconsin?
Under SPS 321.28(4), ice dam protection is required on shingled or shake roofs over a heated area of a dwelling or attached garage with a slope of 4:12 or less. It extends at least 30 inches up the slope from the edge and at least 12 inches beyond the inner face of the exterior wall.
How is a window flashed with house wrap?
In Marvin's method A1, the wrap is cut and folded before the window goes in, a flexible sill pan is installed, the jambs are taped over the fin, a head membrane laps over the jamb tape, and the wrap's head flap is folded down over the head membrane with its diagonal cuts taped.
How many nails per shingle does the Wisconsin code require?
SPS 321.28(3)(a)4 requires at least 4 fasteners per strip shingle or 2 per interlocking shingle, unless the manufacturer has other specifications.
Is there a free printable roofing, siding and windows checklist PDF?
The checklist is a free .xlsx download with no sign-up: a Template sheet with one row per check and a result column, and a Sample sheet with the filled inspection. Excel or Google Sheets saves it as a printable PDF.
The garage kick-out and the dryer duct on job 26-208
The Appleton house left Tuesday's inspection with one wall released and three held. The east wall waits for a kick-out at the garage eave, the west wall for a flashing block around a 12.57-square-inch duct, and the south wall, insulation and siding both, for a patio door under SPS 321.24(2). Each hold has one item to fix and one photo to take before release. The roofing estimate and invoice for job 26-208 come from the free field service templates. A crew that wants the hold photos on the same record as the checklist rows can compare plans on pricing and open Start free trial for 14 days, card not required.